

151 Electrical Power
Generation and Power Line Safety
151.01 Scope
151.02 Definitions Applicable
to This Section
151.03 General Requirements
151.04 Training Requirements
151.05 Job Briefing
151.06 Live-Line Tools
151.07 Overhead Lines
151.08 Live-Line Bare-Hand
Work
151.09 Line Clearance Tree
Trimming Operations

151. ELECTRICAL POWER GENERATION AND POWER LINE SAFETY
01. Scope: (7-1-97)
a. Electrical power generating, transmission, distribution, and related operations and equipment shall conform to all other requirements of this standard as well as the following provisions. Nothing in this standard shall be construed to prohibit better or otherwise safer conditions than specified herein. (7-1-97)
b. This section covers the operation and maintenance of electric power generation, control, transformation, transmission, and distribution lines and equipment. (7-1-97)
02. Definitions: For definitions of other terms used in this section, see sub-section 010 of this standard. (7-1-97)
a. Automatic Circuit Reclosure is a self controlled device for interrupting and reclosing an alternating current circuit with a predetermined sequence of opening and reclosing followed by resetting, hold-closed, or lockout operation. (7-1-97)
b. Bond is the electrical interconnection of conductive parts designed to maintain a common electrical potential. (7-1-97)
c. Cable is a conductor with insulation, or a stranded conductor with or without insulation and other coverings (single conductor cable), or a combination of conductors insulated from one another (multiple conductor cable). (7-1-97)
d. Cable Sheath is a conductive protective covering applied to cables. (7-1-97)
e. Conductor is a material, usually in the form of a wire, cable, or bus bar, used for carrying an electrical current. (7-1-97)
f. De-energized means to be free from any electrical connection to a source of potential difference and from electric charge; not having a potential different from that of the earth. (7-1-97)
g. Energized means to be electrically connected to a source of potential difference, or electrically charged so as to have a potential significantly different from that of earth in the vicinity. (7-1-97)
h. Energy Isolating Device is a physical device that prevents the transmission or release of energy, including, but not limited to, the following: a manually operated electric circuit breaker, a disconnect switch, a manually operated switch, a slide gate, a line valve, blocks, and any similar device with a visible indication of the position of the device. (Push buttons, selector switches, and other control circuit type devices are not energy isolating devices. (7-1-97)
i. Exposed means not isolated or guarded. (7-1-97)
j. Ground is a conducting connecting, whether internal or accidental, between an electric current circuit or equipment and the earth, or to some conducting body that serves in place of the earth. (7-1-97)
k. Guarded means covered, fenced, enclosed, or otherwise protected, by means of suitable covers or casings, barrier rails or screens, mats, or platforms, designed to minimize the possibility, under normal conditions, of dangerous approach or accidental contact by persons or objects. (7-1-97)
l. Insulated means to be separated from other conducting surfaces by a dielectric (including air space) offering a high resistance to the passage of current. (7-1-97)
m. Insulation is that which is relied upon to insulate the conductor from other conducting parts or from ground. (7-1-97)
n. Line Clearance Tree Trimmer is an employee who, through related training or on-the-job experience or both is familiar with the special techniques and hazards involved in line clearance tree trimming. (7-1-97)
o. Lines are conductors used to transmit electric energy and their necessary supporting structures. (7-1-97)
p. Qualified Employee is a person knowledgeable in the construction and operation of the electric power generation, transmission, and distribution equipment involved, along with the associated hazards and has the training required by sub-section 151.04 of this section. (7-1-97)
03. General Requirements: (7-1-97)
a. Existing conditions related to the safety of the work to be performed shall be determined before work on or near electric lines or equipment is started. Such conditions include, but are not limited to, the normal voltages of lines and equipment, the maximum switching transient voltages, the presence of hazardous induced voltages, the presence and condition of protective grounds and equipment grounding conductors, the condition of poles, environmental conditions relative to safety, and the location of circuits and equipment, including power and communication lines and fire protective signaling circuits. (7-1-97)
b. The employer shall provide medical services and first aid as required in section 031 of this standard. (7-1-97)
c. First aid kits shall be available and maintained as required in section 031 of this standard. (7-1-97)
d. Hazardous energy control (lockout/tagout) procedures shall meet the requirements of sub-section 150.12 of this standard. (7-1-97)
e. Confined space entry procedures shall meet the requirements of section 043 of this standard. (7-1-97)
f. Excavation procedures shall meet the requirements of section 044 of this standard. (7-1-97)
g. Personal protective equipment shall meet the requirements of section 050 of this standard. (7-1-97)
h. If, during operation of mechanical equipment, the equipment could become energized, the operation shall also comply with at least one of these requirements: The energized lines exposed to contact shall be covered with insulating protective material that will withstand the type of contact that might be made during the operation. The equipment shall be insulated for the voltage involved and shall be positioned so that its un-insulated portions cannot approach the energized lines or equipment any closer than the minimum approach distances specified in Tables 151.04-A through 151.04-E. Each employee shall be protected from hazards that might arise from equipment contact with energized lines. (7-1-97)
04. Training Requirements: (7-1-97)
a. Employees shall be trained in and familiar with the safety related work practices and other safety related requirements that pertain to their respective job assignments. Employees shall also be trained in and familiar with any other safety practices, including applicable emergency procedures (such as pole top and utility hole rescue), that may not be specifically addressed by this standard but that is related to their work and are necessary for their safety. (7-1-97)
b. Qualified employees shall also be trained and competent in the skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment. They shall have the skills and techniques necessary to determine the nominal voltage of exposed live parts. They shall have the knowledge to determine the minimum approach distances corresponding to the voltages to which the employee will be exposed, see Table 151.04-A through 151.04-E. They shall also be trained in the proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment. Note: For the purposes of this section, a person must have as a minimum this training to be considered a qualified person. (7-1-97)
| TABLE 151.04-A | ||||
| AC LIVE-LINE MINIMUM APPROACH DISTANCE | ||||
| Nominal voltage in kilovolts phase to phase | Distance | |||
| Phase to ground exposure | Phase to phase exposure | |||
| (ft-in) | (m) | (ft-in) | (m) | |
| 0.05 to 1.0 | (4) | (4) | (4) | (4) |
| 1.1 to 15.0 | 2-1 | 0.64 | 2-2 | 0.66 |
| 15.1 to 36.0 | 2-4 | 0.72 | 2-7 | 0.77 |
| 36.1 to 46.0 | 2-7 | 0.77 | 2-10 | 0.85 |
| 46.4 to 72.5 | 3-0 | 0.90 | 3-6 | 1.05 |
| 72.6 to 121 | 3-2 | 0.95 | 4-3 | 1.29 |
| 138 to 145 | 3-7 | 1.09 | 4-11 | 1.50 |
| 161 to 169 | 7-0 | 1.22 | 5-8 | 1.71 |
| 230 to 242 | 5-3 | 1.59 | 7-9 | 2.27 |
| 345 to 362 | 8-6 | 2.59 | 12-6 | 3.80 |
| 500 to 550 | 11-3 | 3.42 | 18-1 | 5.50 |
| 765 to 800 | 14-11 | 4.53 | 26-0 | 7.91 |
| Note
1: These distances take into
consideration the highest switching
surge an employee will be exposed to
on any system with air as the
insulating medium and the maximum
voltages shown.
Note 2: The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges. |
||||
| TABLE 151.04-B | |||||||
| AC LIVE-LINE WORK MINIMUM APPROACH DISTANCE WITH OVER VOLTAGE FACTOR PHASE-TO- GROUND EXPOSURE | |||||||
| Maximum anticipated per-unit transient over-voltage | Distance in feet-inches | ||||||
| Maximum phase-to-phase voltage in kilovolts | |||||||
| 121 | 145 | 169 | 242 | 362 | 552 | 800 | |
| 1.5 | ...... | ...... | ...... | ...... | ...... | 6-0 | 9-8 |
| 1.6 | ...... | ...... | ...... | ...... | ...... | 6-6 | 10-8 |
| 1.7 | ...... | ...... | ...... | ...... | ...... | 7-0 | 11-8 |
| 1.8 | ...... | ...... | ...... | ...... | ...... | 7-7 | 12-8 |
| 1.9 | ...... | ...... | ...... | ...... | ...... | 8-1 | 13-9 |
| 2.0 | 2-5 | 2-9 | 3-0 | 3-10 | 5-3 | 8-9 | 14-11 |
| 2.1 | 2-6 | 2-10 | 3-2 | 4-0 | 5-5 | 9-4 | ...... |
| 2.2 | 2-7 | 2-11 | 3-3 | 4-1 | 5-9 | 9-11 | ...... |
| 2.3 | 2-8 | 3-0 | 3-4 | 4-3 | 6-1 | 10-6 | ...... |
| 2.4 | 2-9 | 3-1 | 3-5 | 4-5 | 6-4 | 11-3 | ...... |
| 2.5 | 2-9 | 3-2 | 3-6 | 4-6 | 6-8 | ...... | ...... |
| 2.6 | 2-10 | 3-3 | 3-8 | 4-8 | 7-1 | ...... | ...... |
| 2.7 | 2-11 | 3-4 | 3-9 | 4-10 | 7-5 | ...... | ...... |
| 2.8 | 3-0 | 3-5 | 3-10 | 4-11 | 7-9 | ...... | ...... |
| 2.9 | 3-1 | 3-6 | 3-11 | 5-1 | 8-2 | ...... | ...... |
| 3.0 | 3-2 | 3-7 | 4-0 | 5-3 | 8-6 | ...... | ...... |
| Note
1: The distance specified in this
table may be applied only where the
maximum anticipated per-unit transient
over voltage has been determined by
engineering analysis and has been
supplied by the employer. Table R-6
applies otherwise.
Note 2: The distances specified in this table are the air, bare-hand, and live-line tool distances. |
|||||||
| TABLE 151.04-C | |||||||
| AC LIVE-LINE WORK MINIMUM APPROACH DISTANCE WITH OVER VOLTAGE FACTOR PHASE-TO-PHASE EXPOSURE | |||||||
| Maximum anticipated per-unit transient over-voltage | Distance in feet-inches | ||||||
| Maximum phase-to-phase voltage in kilovolts | |||||||
| 121 | 145 | 169 | 242 | 362 | 552 | 800 | |
| 1.5 | ...... | ...... | ...... | ...... | ...... | 7-4 | 12-1 |
| 1.6 | ...... | ...... | ...... | ...... | ...... | 8-9 | 14-6 |
| 1.7 | ...... | ...... | ...... | ...... | ...... | 10-2 | 17-2 |
| 1.8 | ...... | ...... | ...... | ...... | ...... | 11-7 | 19-11 |
| 1.9 | ...... | ...... | ...... | ...... | ...... | 13-2 | 22-11 |
| 2.0 | 3-7 | 4-1 | 4-8 | 6-1 | 8-7 | 14-10 | 26-0 |
| 2.1 | 3-7 | 4-2 | 4-9 | 6-3 | 8-10 | 15-7 | ...... |
| 2.2 | 3-8 | 4-3 | 4-10 | 6-4 | 9-2 | 16-4 | ...... |
| 2.3 | 3-9 | 4-4 | 4-11 | 6-6 | 9-6 | 17-2 | ...... |
| 2.4 | 3-10 | 4-5 | 5-0 | 6-7 | 9-11 | 18-1 | ...... |
| 2.5 | 3-11 | 4-6 | 5-2 | 6-9 | 10-4 | ...... | ...... |
| 2.6 | 4-0 | 4-7 | 5-3 | 6-11 | 10-9 | ...... | ...... |
| 2.7 | 4-1 | 4-8 | 5-4 | 7-0 | 11-2 | ...... | ...... |
| 2.8 | 4-1 | 4-9 | 5-5 | 7-2 | 11-7 | ...... | ...... |
| 2.9 | 4-2 | 4-10 | 5-6 | 7-4 | 12-1 | ...... | ...... |
| 3.0 | 4-3 | 4-11 | 5-8 | 7-6 | 12-6 | ...... | ...... |
| Note
1: The distance specified in this
table may be applied only where the
maximum anticipated per-unit transient
over voltage has been supplied by the
employer. Table R-6 applies otherwise.
Note 2: The distances specified in this table are the air, bare-hand, and live-line tool distances. |
|||||||
| TABLE 151.04-D | |||||
| DC LIVE-LINE WORK MINIMUM APPROACH DISTANCE WITH OVER VOLTAGE FACTOR | |||||
| Maximum anticipated per-unit transient over voltage | Distance in feet-inches | ||||
| Maximum lin-to-ground voltage in kilovolts | |||||
| 250 | 400 | 500 | 600 | 750 | |
| 1.5 or lower | 3-8 | 5-3 | 6-9 | 8-7 | 11-10 |
| 1.6 | 3-10 | 5-7 | 7-4 | 9-5 | 13-1 |
| 1.7 | 4-1 | 6-0 | 7-11 | 10-3 | 14-4 |
| 1.8 | 4-3 | 6-5 | 8-7 | 11-2 | 15-9 |
| Note
1: The distances specified in this
table may be applied only where the
maximum anticipated per-unit transient
over voltage has been determined by
engineering analysis and has been
supplied by the employer. However, if
the transient over voltage factor is
not known, a factor of 1.8 shall be
assumed.
Note 2: The distances specified in this table are the air, bare-hand, and live-line tool distances. |
|||||
| TABLE 151.04-E | |||||
| ALTITUDE CORRECTION FACTOR | Correction Factor | ||||
| ft | ft | m | m | ||
| 3000 | 10000 | 900 | 3000 | 1.00 | 1.20 |
| 4000 | 12000 | 1200 | 3600 | 1.02 | 1.25 |
| 5000 | 14000 | 1500 | 4200 | 1.05 | 1.30 |
| 6000 | 16000 | 1800 | 4800 | 1.08 | 1.35 |
| 7000 | 18000 | 2100 | 5400 | 1.11 | 1.39 |
| 8000 | 20000 | 2400 | 6000 | 1.14 | 1.44 |
| 9000 | 2700 | 1.17 | |||
| Note 1: If the work is performed at elevations greater than 3000 ft (900 m) above sea level, the minimum approach distance shall be determined by multiplying the distance in Table 151.04-A through Table 151.04-E by the correction factor corresponding to the altitude at which work is performed. | |||||
c. The employer shall determine, through regular supervision and through inspections conducted on at least an annual basis, that each employee is complying with safety related work practices. (7-1-97)
d. An employee shall receive additional training or retraining under any of the following conditions: it the supervisory or annual inspections indicate that the employee is not complying with safety related work practices; or if new technology, new types of equipment , or changes in procedures necessitate the use of safety related work practices that are different from those which the employee would normally use; or if the employee safety related work practices that are not normally used during the employee's regular job duties. Note: Tasks that are performed less often than once per year shall necessitate retraining before the performance of the work practices involved. (7-1-97)
e. Training required by this section shall be of the classroom or on-the-job type. (7-1-97)
f. The training shall establish employee proficiency in the work practices required by this section and shall introduce the procedures necessary for compliance with this section. (7-1-97)
05. Job Briefing: (7-1-97)
a. The employer shall ensure that the employee in charge of a job conducts a job briefing with the employees involved before they start each job. The briefing shall cover at least the following subjects: hazards associated with the job, work procedures involved, special precautions, energy source controls, and personal protective equipment requirements. (7-1-97)
b. If the work or operations to be performed during the work day or shift are repetitive and similar, at least one job briefing shall be conducted before the start of the first job of each day or shift. Additional job briefings shall be held if significant changes, which might affect the safety of the employees, occur during the course of the work. A brief discussion is satisfactory if the work involved is routine and if the employee, by virtue of training and experience, can reasonably be expected to recognize and avoid the hazards involved in the job. A more extensive discussion shall be conducted: if the work is complicated or particularly hazardous, or if the employee cannot be expected to recognize and avoid the hazards involved in the job. Note: The briefing is always required to touch on all the subjects listed in sub-section 151.05.a above. (7-1-97)
c. An employee working alone need not conduct a job briefing. However, the employer shall ensure that the tasks to be performed are planned as if a briefing were required. (7-1-97)
06. Live-Line Tools: (7-1-97)
a. Live-line tool rods, tubes, and poles shall be designed and constructed to withstand the following minimum tests: (7-1-97)
i. One-hundred-thousand (100,000) volts per foot of length for five (5) minutes if the tool is made of fiberglass reinforced plastic (FRP); (7-1-97)
ii. Seventy-five-thousand (75,000) volts per foot of length for three (3) minutes if the tool is made of wood; (7-1-97)
iii. Or other tests that the employer can demonstrate are equivalent. (7-1-97)
b. Each live-line tool shall be wiped clean and visually inspected for defects before use each day. If any defect or contamination that could adversely affect the insulating qualities or mechanical integrity of the live-line tool is present after wiping, the tool shall be removed from service and examined and tested to the requirements of sub-section 151.06.a above before being returned to service. (7-1-97)
c. The examination, cleaning, repairing, and in-service testing of live-line tools shall be in accordance with the guidelines contained in the Institute of Electrical and Electronics Engineers Guide for In service Maintenance and Electrical Testing of Live-Line Tools, IEEE Std. 978. (7-1-97)
07. Overhead Lines: (7-1-97)
a. Before elevated structures, such as poles or towers, are subjected to such stresses as climbing or the installation or removal of equipment may impose, the employer shall ascertain that the structures are capable of sustaining the additional or unbalanced stresses. If the pole or other structure cannot withstand the loads which will be imposed it shall be braced or otherwise supported so as to prevent failure. (7-1-97)
b. When poles are set, moved, or removed near exposed energized overhead conductors, the pole shall not contact the conductors. (7-1-97)
c. When a pole is set, moved, or removed near an exposed energized overhead conductor, the employer shall ensure that each employee wears electrical protective equipment and uses insulated devices when handling the pole and that no employee contacts the pole with un-insulated parts of their body. (7-1-97)
d. To protect employees from falling into holes into which poles are to be placed, the holes shall be attended by employees or physically guarded whenever anyone is working nearby. (7-1-97)
e. When installing or removing overhead lines the employer shall use the tension stringing method, barriers, or other equivalent measures to minimize the possibility that conductors and cables being installed or removed will contact energized power lines or equipment. (7-1-97)
f. The protective measures required by sub-section 151.04.h of this section shall also be provided for conductors, cables, and pulling and tensioning equipment when the conductor or cable is being installed or removed close enough to energized conductors that any of the following failures could energize the pulling or tensioning equipment or the wire or cable being installed or removed: failure of the pulling or tensioning equipment, failure of the wire or cable being pulled, or failure of the previously installed lines or equipment. (7-1-97)
g. If the conductors being installed or removed cross over energized conductors in access of six-hundred (600) volts and if the design of the circuit-interrupting device protecting the lines so permits, the automatic reclosing feature of these devices shall be made inoperative. (7-1-97)
h. Before lines are installed parallel to existing energized lines, the employer shall make a determination of the approximate voltage to be induced in the new lines, or work shall proceed on the assumption that the induced voltage is hazardous. Unless the employer can demonstrate that the lines being installed or removed are not subject to the induction of hazardous voltage or unless the lines are treated as energized, the following requirements also apply: (7-1-97)
i. Each bare conductor shall be grounded in increments so that no point along the conductor is more than two (2) miles from a ground. (7-1-97)
ii. The grounds shall be left in place until the conductor installation is completed between dead ends. (7-1-97)
iii. The grounds shall be removed as the last phase of aerial cleanup. (7-1-97)
iv. If employees are working on bare conductors, grounds shall also be installed at each location where these employees are working, and grounds shall be installed at all open dead-end or catch-off points to the next adjacent structure. (7-1-97)
v. If two bare conductors are to be spliced, the conductors shall be bonded and grounded before being spliced. (7-1-97)
i. Reel handling equipment, including pulling and tensioning devices, shall be in safe operating condition and shall be leveled and aligned. (7-1-97)
j. Load rating of stringing, pulling lines, conductor grips, load bearing hardware and accessories, rigging, and hoists shall not be exceeded. (7-1-97)
k. Pulling lines and accessories shall be repaired or replaced when defective. (7-1-97)
l. Conductor grips shall not be used on wire rope, unless the grip is specifically designed for this application. (7-1-97)
m. Reliable communications, through two-way radios or other equivalent means, shall be maintained between the reel tender and the pulling rig operator. (7-1-97)
n. The pulling rig shall only be operated when it is safe to do so. Examples of unsafe conditions include employees in locations prohibited by sub-section 151.07.o of this section, conductor and pulling line hang-ups, and slipping of the conductor grip. (7-1-97)
o. While the conductor or pulling line is being pulled (in motion) with a power driven device, employees shall not be permitted directly under overhead operations or on the cross arm, except as necessary to guide the stringing sock or board over or through the stringing sheave. (7-1-97)
08. Live-Line Bare-Hand Work: (7-1-97)
a. Live-line bare-hand work shall be conducted under all other applicable provisions of section 151 of this standard in addition to the specific requirements of this sub-section. (7-1-97)
b. Before any employee uses the live-line bare-hand technique on energized high-voltage conductors or parts, the following information shall ne ascertained: the nominal voltage rating of the circuit on which the work is to be performed; the minimum approach distances to ground from lines and other energized parts on which work is to be performed; and the voltage limitations of equipment to be used. (7-1-97)
c. The insulated equipment, insulated tools, and aerial devices and platforms used shall be designed, tested, and intended for live-line bare-hand work. Tools and equipment shall be keep clean and dry while they are in use. (7-1-97)
d. The automatic reclosing feature of circuit interrupting devices protecting the lines shall be made inoperative, if the design of the devices permits. (7-1-97)
e. Work shall not be performed when adverse weather conditions such as thunderstorms in the immediate vicinity, high winds, snow storms, and ice storms, would make the work hazardous even after the work practices required by this section are employed. Additionally, work shall not be performed when the winds reduce the phase-to-phase or phase-to- ground minimum approach distances at the work location below that specified in sub-section 151.08.m of this section, unless the grounded objects and other lines and equipment are covered by insulating guards. (7-1-97)
f. A conductive bucket liner or other conductive device shall be provided for bonding the insulated aerial device to the energized line or equipment. The employee shall be connected to the bucket liner or other conductive device by the use of conductive shoes, leg clips, or other means. Where differences in potentials at the work-site pose a hazard to employees, electrostatic shielding designed for the voltages being worked shall be provided. (7-1-97)
g. Before the employee contacts the energized part, the conductive bucket liner or other conductive device shall be bonded to the energized conductor by means of a positive connection. This connection shall remain attached to the energized conductor until the work on the energized circuit is completed. (7-1-97)
h. Aerial lifts to be used for live-line bare-hand work shall have dual controls (lower and upper) as follows: The upper controls shall be within easy reach of the employee in the bucket. On a two (2) bucket-type lift, access to the controls shall be within easy reach from either bucket. The lower set of controls shall be located near the base of the boom, and shall be so designed that they can override the operation of the equipment at any time. (7-1-97)
i. Lower (ground-level) lift controls shall not be operated with an employee in the lift, except in an emergency. (7-1-97)
j. Before employees are elevated into the work position, all controls (ground level and bucket) shall be checked to determine that they are in proper working condition. (7-1-97)
k. Before the boom of an aerial lift is elevated, the body of the truck shall be grounded, or the body of the truck shall be barricaded and treated as energized. (7-1-97)
l. A boom current test shall be made before work is started each day, each time during the day when higher voltage is encountered, and when changed conditions indicate a need for an additional test. This test shall consist of placing the bucket in contact with an energized source equal to the voltage to be encountered for a minimum of three (3) minutes. The leakage current shall not exceed one (1) micro-ampere per kilovolt of nominal phase-to-ground voltage. Work from the aerial lift shall be immediately suspended upon indication of a malfunction in the equipment. (7-1-97)
m. The minimum approach distances specified in Tables 151.04-A through 151.04-E shall be maintained from all grounded objects and from lines and equipment at a potential different from that to which the live-line bare-hand equipment is bonded, unless such grounded objects and other lines and equipment are covered by insulating guards. (7-1-97)
n. While an employee is approaching, leaving, or bonding to an energized circuit, the minimum approach distances in Tables 151.04-A through 151.04-E shall be maintained between employees and any grounded parts, including the lower boom and portions of the truck. (7-1-97)
o. While the bucket is positioned alongside an energized bushing or insulator string, the phase-to-ground minimum approach distances of Tables 151.04-A through 151.04-E shall be maintained between all parts of the bucket and the grounded end of the bushing or insulator string or any other grounded surface. (7-1-97)
p. Hand lines shall not be used between the bucket and the boom or between the bucket and the ground. However, non-conductive type hand lines may be used from conductor to ground if not supported from the bucket. Ropes used for live-line bare-hand work shall not be used for other purposes. (7-1-97)
q. Un-insulated equipment or material shall not be passed between a pole or structure and an aerial lift while an employee working from the bucket is bonded to an energized part. (7-1-97)
r. A minimum approach distance table reflecting the minimum approach distances listed in Tables 151.06-A through 151.04-E shall be printed on a plate of durable non-conductive material. This table shall be mounted so as to be visible to the operator of the boom. (7-1-97)
s. A non-conductive measuring device shall be readily accessible to assist employees in maintaining the required minimum approach distance. (7-1-97)
09. Line Clearance Tree Trimming Operations: (7-1-97)
a. Before an employee climbs, enters, or works around any tree, a determination shall be made of the nominal voltage of electrical power lines posing a hazard to employees. However, a determination of the maximum nominal voltage to which an employee may be made instead, if all lines are considered as energized at this maximum voltage. (7-1-97)
b. There shall be a second line clearance tree trimmer within normal (that is unassisted) voice communication under any of the following conditions: (7-1-97)
i. If a line clearance tree trimmer is to approach more closely than 10-feet to any conductor energized to more than 750-volts; (7-1-97)
ii. If branches or limbs being removed are closer to lines energized at more than 750-volts than the distances listed in Tables 151.04-A, 151.04-D, and 151.04-E; (7-1-97)
iii. Or if roping is necessary to remove branches or limbs from such energized conductors or apparatus. (7-1-97)
c. Line clearance tree trimmers shall maintain the minimum approach distances from energized conductors given in Tables 151.04-A, 151.04-D, and 151.04-E. (7-1-97)
d. Branches that are contacting exposed energized conductors or equipment or that are within the distances specified in Tables 151.04-A, 151.04-D, and 151.04-E shall be removed only through the use of insulating equipment listed in Subsection 151.06 of this section. (7-1-97)
e. Ladders, platforms, and aerial devices shall not be brought closer to an energized part than the distances listed in Tables 151.04-A, 151.04-D, and 151.04-E. (7-1-97)
f. Line clearance tree trimming work shall not be performed when adverse weather conditions such as thunderstorms in the immediate vicinity, high winds, snow storms, and ice storms, make the work hazardous in spite of the work practices required by this subsection. Each employee performing line clearance tree trimming work in the aftermath of a storm or other similar emergency conditions shall be trained in the special hazards related to this type of work. (7-1-97)
152. --
159. (RESERVED)