               |
 |
NEC Editions and Exceptions
NFPA 70 - NATIONAL ELECTRICAL CODE
(NEC)
The National
Fire Protection Association provides
Article 70, the NEC and publishes a revised
edition every three years. Idaho Code
establishes the National Electrical Code
(NEC) as the safety standard for electrical
installations in the state of Idaho. Under
those provisions, the National Electrical
Code, 2008 Edition, as adopted by the Idaho
State Electrical Board, is in full force and
effect on and after July 1, 2008, with the
exception of the
following:
- Compliance with Article 675.8(B) will
include the additional requirement that
a disconnecting means always be provided
at the point of service from the utility
no matter where the disconnecting means
for the machine is located.
- Compliance with Article 550.32(B)
shall limit installation of a service on
a manufactured home to those homes
manufactured after January 1, 1992.
- Compliance with Article 210.12(B) shall only apply to bed rooms and the fire/smoke alarm branch circuit outlets.
- d.Poles used as lighting standards that are forty (40) feet or less in nominal height and that support no more than four (4) luminaries operating at a nominal voltage of three hundred (300) volts or less, shall not be considered to constitute a structure as that term, is defined by the National Electrical Code (NEC). The disconnecting means shall not be mounted to the pole. The disconnecting means may be permitted elsewhere in accordance with NEC, Article 225.32, exception 3. SEC special purpose fusible connectors (model SEC 1791-DF or model SEC 1791-SF) or equivalent shall be installed in a listed hand hole (underground) enclosure. The enclosure shall be appropriately grounded and bonded per the requirements of the NEC applicable to Article 230-Services. Over current protection shall be provided by a (fast-acting - minimum - 100K RMS Amps 600 VAC) rated fuse. Wiring within the pole for the luminaries shall be protected by supplementary over current device(s) (time-delay - minimum - 10K RMS Amps 600 VAC) in break-a-away fuse holder(s) accessible from the hand hole. Any poles supporting or incorporating utilization equipment or exceeding the prescribed number of luminaries, or in excess of forty(40) feet, shall be considered structures, and an appropriate service disconnecting means shall be required per the NEC. All luminary-supporting poles shall be appropriately grounded and bonded per the NEC.
Refer to Light Pole Installation and
Inspection Procedures, under Important
Informational Notices for more
specifics.
-
e. Compliance with Article 680.26 Bonding.
i. Performance. The bonding required by this section shall be installed to eliminate voltage gradients in the pool area as prescribed. FPN: This section does not require that the eight (8) AWG or larger solid copper bonding conductor be extended or attached to any remote panelboard, service equipment, or any electrode.
ii. Bonded Parts. The parts specified in 680.26(B)(1) through (B)(5) shall be bonded together.
(1) Metallic Structural Components. All metallic parts of the pool structure, including the reinforcing metal of the pool shell, coping stones, and deck, shall be bonded. The usual steel tie wires shall be considered suitable for bonding the reinforcing steel together, and welding or special clamping shall not be required. These tie wires shall be made tight. If reinforcing steel is effectively insulated by an encapsulating nonconductive compound at the time of manufacture and installation, it shall not be required to be bonded. Where reinforcing steel is encapsulated with a nonconductive compound, provisions shall be made for an alternate means to eliminate voltage gradients that would otherwise be provided by unencapsulated, bonded reinforcing steel.
(2) Underwater Lighting. All forming shells and mounting brackets of no-niche luminaries (fixtures) shall be bonded unless a listed low-voltage lighting system with nonmetallic forming shells not requiring bonding is used.
(3) Metal Fittings. All metal fittings within or attached to the pool structure shall be bonded. Isolated parts that are not over one hundred (100) mm (four (4) inches) in any dimension and do not penetrate into the pool structure more than twenty-five (25) mm (one (1) inch) shall not require bonding.
(4) Electrical Equipment. Metal parts of electrical equipment associated with the pool water circulating system, including pump motors and metal parts of equipment associated with pool covers, including electric motors, shall be bonded. Metal parts of listed equipment incorporating an approved system of double insulation and providing a means for grounding internal nonaccessible, non-current-carrying metal parts shall not be bonded. Where a double-insulated water-pump motor is installed under the provisions of this rule, a solid eight (8) AWG copper conductor that is of sufficient length to make a bonding connection to a replacement motor shall be extended from the bonding grid to an accessible point in the motor vicinity. Where there is no connection between the swimming pool bonding grid and the equipment grounding system for the premises, this bonding conductor shall be connected to the equipment grounding conductor of the motor circuit.
(5) Metal Wiring Methods and Equipment. Metal-sheathed cables and raceways, metal piping, and all fixed metal parts except those separated from the pool by a permanent barrier shall be bonded that are within the following distances of the pool:
(a) Within one and five tenths (1.5) meters (five (5) feet) horizontally of the inside walls of the pool.
(b) Within three and seven tenths (3.7) meters (twelve (12) feet) measured vertically above the maximum water level of the pool, or any observation stands, towers, or platforms, or any diving structures.
iii. Common Bonding Grid. The parts specified in 680.26B shall be connected to a common bonding grid with a solid copper conductor, insulated, covered, or bare, not smaller than eight (8) AWG. Connection shall be made by exothermic welding or by pressure connectors or clamps that are labeled as being suitable for the purpose and are of stainless steel, brass, copper, or copper alloy. The common bonding grid shall be permitted to be any of the following:
(1) The structural reinforcing steel of a concrete pool where the reinforcing rods are bonded together by the usual steel tie wires or the equivalent.
(2) The wall of a bolted or welded metal pool.
(3) A solid copper conductor, insulated, covered, or bare, not smaller than eight (8) AWG.
(4) Rigid metal conduit or intermediate metal conduit of brass or other identified corrosion-resistant metal conduit.
iv. Connections. Where structural reinforcing steel or the walls of bolted or welded metal pool structures are used as a common bonding grid for nonelectrical parts, the connections shall be made in accordance with 250.8.
v. Pool Water Heaters. For pool water heaters rated at more than fifty (50) amperes that have specific instructions regarding bonding and grounding, only those parts designated to be bonded shall be bonded, and only those parts designated to be grounded shall be grounded.
A copy of the current edition of the NEC
is available for reference at the office of
the Division of Building Safety, Electrical
Bureau 1090 E. Watertower St., Meridian,
Idaho. NEC books may be obtained
online, at some electrical supply houses
and bookstores.
|
 |
 
Electrical Bureau
1090 E. Watertower St.
Meridian, ID 83642
Ph 208-334-2183
Fax 208-855-2165
Code & License Info 800-955-3044
|